Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March 23
2.3.5.2. Jumper Position for Termination Resistance
With multiple inverters connected, the jumper located behind the CAN bus terminal activates
the termination resistance when the pins are short-circuited, which minimizes signal
reflections in the cables and avoids interference.
Single inverter: The two pins must be short-circuited (Default).
Multiple inverters connected: The master-slave configuration requires short-circuited pins
on the first inverter and on the last inverter in the linked series. The pins must be
disconnected on the inverters between the first and last inverters in the linked series.
To disconnect the pins, the jumper must be pulled up and placed only on one of the pins.
Be careful not to bend the pins when removing or installing the jumper!
Table 2.3.2: Jumper for multiple inverters in linked series
Connection Area
From the
side
From
above
Pins
The pins are short-
circuited.
The pins are
disconnected.
2.4. Safety Equipment Required for Grid Connected
Systems
Safety equipment includes switches or circuit breakers to disconnect power sources, fuses
or circuit breakers to protect conductors from overheating and surge protection to protect
the equipment from voltage bursts and surges.
NOTICE
Safety Equipment: The system installer is responsible for providing safety equipment that
meets the requirements for both the DC and AC operations to protect the equipment and
prevent personal injury.
Refer to User Guide for detailed information about rating and installation of the
safety equipment.